1.1 These test methods determine the time of setting of
hydraulic cement by means of the Vicat needle. Two test
methods are given; Test Method A is the Reference Test
Method using the manually operated standard Vicat apparatus,
while Test Method B permits the use of an automatic Vicat
machine that has, in accordance with the qualification requirements of this method, demonstrated acceptable performance.
1.2 The values stated in SI units are to be regarded as
standard. No other units of measurement are included in this
standard.
1.3 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
(Warning—Fresh hydraulic cementitious mixtures are caustic
and may cause chemical burns to skin and tissue upon
prolonged exposure.)2
1.4 The text of these test methods reference notes and
footnotes which provide explanatory material. These notes and
footnotes (excluding those in tables and figures) shall not be
considered as requirements of the standard.
NOTE 1—For the test method for determining the time of setting by
Gillmore needles, see Test Method C266.
1.5 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical
Barriers to Trade (TBT) Committee.
|
|
|
|