Technical Committee No |
TC06 |
|
Status |
Replaced |
|
Category |
Construction and Building Sector |
|
Sub Category |
|
|
$Resources:StandardType; |
Kuwaiti Standard |
1.1 This specification establishes the requirements for Type
GAS seamless Copper UNS No. C12200 tube for use in above
ground natural gas and liquified petroleum (LP) gas fuel
distribution systems, commonly assembled with flared fittings
or brazed joints.
1.2 O60 (soft annealed) temper gas tube is produced in the
range of standard sizes 3?8– to 7?8–in. outside diameter; H58
(drawn general purpose) temper gas tube is produced in the
range of standard sizes 3?8– to 11?8–in. outside diameter.
1.3 O60 (soft annealed) temper gas tube systems are normally
assembled with single 45° flared fittings, although
brazed connections using wrought or cast fittings may be
permitted by local or code requirements. H58 (drawn general
purpose) temper gas tube systems are assembled with brazed
connections.
NOTE 1—Tube temper and applicable size are determined by installation
code requirements.
1.4 Flared fittings used with seamless copper tube for
natural gas and liquified petroleum (LP) gas fuel distribution
systems shall be free of residual stresses.
1.5 The values stated in inch-pound units are standard. SI
values given in parentheses are for information only.
|
|
|
|
Decision No |
37/2010 |
|
|
Decision By |
From Ministers Office |
|
|
Date of Meeting |
17-10-2009 |
|
|
Approval Date |
15-09-2010 |
|
|
Decision Date |
|
|
|
Newspaper Publication Date |
19-10-2010 |
|
|
Newspaper Number |