1.1 This specification covers the minimum requirements for
full-thickness (in accordance with Table 1) interior gypsum
plastering on gypsum, metal, masonry, or monolithic concrete
bases designed or prepared to receive gypsum plaster.
1.1.1 Gypsum plaster applied to the interior side of exterior
walls of masonry or concrete shall be isolated from the exterior
wall.
1.2 Gypsum plasters shall not be used in exterior locations
or interior “wet” areas.
NOTE 1—To secure desirable results, this specification should be
coordinated with the provisions of Specification C 841. General information
concerning full thickness gypsum plastering is contained in Annex
A2, Annex A3, and Annex A4.
1.3 Details of construction for a specific assembly to
achieve the required fire resistance shall be obtained from
reports of fire-resistance tests, engineering evaluations, or
listings from recognized fire testing laboratories.
1.4 Details of construction to achieve required sound control
shall be obtained from reports of tests conducted at
recognized sound testing laboratories in accordance with the
applicable sound tests of Test Methods E 90, C 423, or E 492.
1.5 The values stated in inch-pound units are to be regarded
as the standard. The SI (metric) values given in parentheses are
approximate and are provided for information purposes only.
1.6 The text of this standard references notes and footnotes
which provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered
as requirements of the standard.
|
|
|
|